219/348
Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the heating engineer settings
18.10.2002
4.199 Composite outside temperature TAxgem
•
Compensating variable for the flow temperature control
The composite outside temperature is a mixture of the actual outside temperature and
the attenuated outside temperature as calculated by the controller.
This operating line automatically displays the actual value [°C] of the composite outside
temperature. No direct setting can be made.
Display
Unit
-50...50 °C
The mixture of actual and attenuated outside temperature is dependent on the type of
building construction (setting 725) and is generated as follows:
Selected type of construction
Composite outside temperature
Heavy (setting 725 = 0)
Tagem = ½ TAakt + ½ TAged
Light (setting 725 = 1)
Tagem = ¾ TAakt + ¼ TAged
The composite outside temperature as a compensating variable acts on flow tempera-
ture control, that is thus matched to the prevailing weather conditions.
It also acts on the 24-hour heating limit to shut down the heating.
TAakt
Actual outside temperature
TAged
Attenuated outside temperature
TAgem1
Composite outside temperature for light building structures
TAgem0
Composite outside temperature for heavy building structures
Benefit
Description
Setting
Process
Effect
Example
13
14
15
16
17
23
71
D12
18:00
06:00
06:00
18:00
18:00
t
TA
TAakt
TAged
°C
TAgem1
TAgem0