Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the enduser settings
18.10.2002
Setting the clock
•
Automatic changeover from summer- to wintertime, and vice versa
•
Fast and easy-to-understand time settings
•
Leap years are taken into consideration
To ensure correct operation of the switching programs, the time of day, weekday, date
and year must be correctly set.
Knowledge of date and year also allows the controller to provide automatic summer- /
wintertime changeover, to consider leap years and to ensure the correct triggering of
the holiday program.
The time of day can be set from a remote location via the bus system, provided clock
operation is appropriately set. Also refer to clock operation on operating line 865.
3.7 Time
of
day
Setting range
Unit
00:00...23:59
Hour : Minute
•
During the setting procedure, the clock continues to run
•
Each time the + or - button is pressed, the seconds are reset to zero
3.8 Weekday
Setting range
Unit
1...7 Weekday
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday
3.9 Date (day / month) and year
Setting range
Unit
01.01...31.12 Weekday
month
Setting range
Unit
2001...2094 Year
Benefit
Description
System time
Notes
Weekday table