HVAC Products
Description of the EXP settings 18.10.2002
5.62 Switching differential of the d.h.w.
temperature (SDBW)
•
Optimum frequency of d.h.w. heating
D.h.w. control is in the form of a two-position controller with an adjustable switching
differential.
The switching differential used for d.h.w. control does not affect d.h.w. heating with a
control thermostat.
Setting range
Unit
Factory setting
0...20 K
5
The setting will change the switching differential of the d.h.w. temperature control.
Entry:
Increase:
Switching differential will become larger
Fewer and longer heating up times, larger temperature variations
Decrease:
Switching differential will become smaller
More frequent and shorter heating up times, smaller temperature varia-
tions
D.h.w. temperature control
2-position control heats the d.h.w. at certain intervals. The duration of d.h.w. heating
depends mainly on the storage tank’s capacity and water volume and the amount of
d.h.w. currently required.
D.h.w. ON:
TBWx = TBWw - SDBW
D.h.w. OFF:
TBWx = TBWw
°C
23
91
Z
33
ON
OFF
w
TBWx [
]
P
Benefit
Description
Note
Setting
Effect
OFF
ON
P
°C
TBWx
TBWw
23
71
D05
TBWw-SDBW
t
Legend
TBWx
Actual value of d.h.w. tempe-
rature
TBWw
D.h.w temperature setpoint
SDBW
Switching differential of d.h.w.
ON
Switch-on point
OFF
Switch-off point
t
Time
P
Pump
Switching differential
P
Pump (ON / OFF)
w Setpoint
Switch-on
point
Switch-off
point