4.210 Locking signal gain heating circuit
•
Matching the system to different types of boilers and plant conditions
The effect of the locking signal can be amplified or attenuated.
Setting range
Unit
Factory setting
0...200 %
100
The gain is adjustable between 0 % and 200 %. The setting changes the response of
the mixing heating circuit to restrictions imposed by the locking signal. Also refer to
"mixing valve restriction" in Index.
Setting Response
0 %
Locking signal will be ignored
1...99 %
Locking signal will be reduced
100 %
Locking signal will be adopted unchanged
101...200 %
Locking signal will be amplified up to 2 times
4.211 Frost protection for the plant with the heating
circuit pump
“Frost protection for the plant with the heating circuit pump” can be switched on and off.
Setting range
Unit
Factory setting
0 / 1
–
1
0
The “General frost protection for the plant“
does not act
on the pump of the
heating circuit.
1
The “General frost protection for the plant“
acts
on the pump of the heating cir-
cuit.
If the “General frost protection for the plant” (operating line 180
EXP
) is switched off, the
setting made on this operating line (732) has no impact.
A detailed description of the impact of frost protection for the plant is given on operating
line 180
EXP
.