CE1P2488en
HVAC Products
Description of the heating engineer settings
18.10.2002
4.136 Heat pump switching differential ON
•
Defines the heat pump’s switch-on point
As soon as the temperature at the selected sensor (operating line 420) drops below the
setpoint by the switching differential adjusted here (operating line 400 or 402), the heat
pump will be released for operation.
Setting range
Unit
Factory setting
1...20 K
2
0
1
23
92D
04
t
T
WF
400
Display of heat pump’s flow temperature setpoint
401
Actual value of the heat pump flow temperature
402
Display of heat pump’s return temperature setpoint
403
Actual value of the heat pump return temperature
421
Heat pump switching differential ON
422
Heat pump switching differential OFF
WF
Release of heat pump (0 = no released, 1 = released)
The minimum compressor off time (operating line 414
EXP
), the minimum compressor on
time (operating line 413
EXP
) and compensation of the running time-dependent surplus
heat / heat deficit (operating line 416
EXP
) can considerably delay the switch-on / off time
(according to the switching differentials ON and OFF, operating lines 421 and 422).
4.137 Heat pump switching differential OFF
•
Defines the heat pump’s switch-off point
The heat pump will be switched off as soon as the temperature at the selected sensor
(operating line 420) exceeds the setpoint by the switching differential adjusted here
(operating line 400 or 402).
Setting range
Unit
Factory setting
1...20 K
2
Refer to graph on operating line 421.
The minimum compressor off time (operating line 414
EXP
), the minimum compressor
running time (operating line 413
EXP
) and compensation of the running time-related sur-
plus heat / heat deficit (operating line 416
EXP
) can significantly delay the switch-on / off
point (according to switching differentials ON and OFF, operating lines 421 and 422).