277/348
Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the EXP settings
18.10.2002
5 Description of the EXP settings
For an overview of the settings and the setting procedure, refer to page 49.
EXP general
5.1 General frost protection for the plant
•
Protects the plant against freezing
When there is a risk of frost, the controller will activate all released pumps of the plant,
thus protecting the heating plant against freeze-ups.
The “General frost protection for the plant” overrides frost protection for the individual
plant components. When “General frost protection for the plant” is deactivated, “Frost
protection by pump operation” will be suppressed for all plant components – on the
other hand, when “General frost protection for the plant” is active, frost protection for
the individual plant components can be switched on an individual basis.
Prerequisite for the proper functioning of “General frost protection for the plant” is a fully
operational plant that works properly. Frost protection for the plant is possible only
when an outside sensor is connected (controller-internal or LPB).
Setting range
Unit
Factory setting
0 / 1
–
1
Depending on the selection made, the plant will be protected by activating the pumps.
In that case, the heat sources will
not
be put into operation.
The heat sources are put into operation only if this is demanded either by frost protec-
tion according to the component temperature (refer to chapter 6 “Frost protection”), or
by frost protection for the building (according to the room temperature, operating line
28).
Entry:
0
Frost protection for the plant
OFF
Function deactivated
An outside sensor is not necessarily required
1
Frost protection for the plant
ON
Function activated All released pumps according to the description given below
are operating. When there is no outside temperature value, operating line 50 will
display error message 10.
The pumps acted upon by frost protection for the plant can be individually excluded:
•
Frost protection for the plant
with the pump of the oil- / gas-fired boiler
Operating line 271
•
Frost protection for the plant
with the pump of the wood-fired boiler
Operating line 378
•
Frost protection for the plant
with the heating circuit pump
Operating line 732
•
Frost protection for the plant
with the system pump
Operating line 803
Benefit
Description
Important
Setting
Effect