134/348
Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the heating engineer settings
18.10.2002
In this example, the switch-on point lies below the switch-off point.
OFF
ON
B8
239
2D
03
t
T
Assignment of relay K17 to a free relay terminal is made on operating line 154.
4.58 Switch-off temperature flue gas temperature
sensor function (ZuFu10)
If the actual value of flue gas temperature B8 (operating line 222) reaches the tem-
perature adjusted here, relay K17 of the flue gas temperature function will be deener-
gized. This means that the controlled flue gas temperature function will be deactivated.
Display
Unit
Factory setting
0...350 °C
40
(Refer to operating line 225).
Assignment of relay K17 to a free relay terminal is made on operating line 154.
Example of flue gas fan
Note
Description
Setting
Use
Note