37/348
Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Handling
18.10.2002
Line Function
Range
Unit
Resolution Factory
setting
Terminal test
210 Output test
(relay test)
---
Control mode according to the operating state
0
All outputs OFF
1 Q101
ON
2 Q102
ON
3 Q103
ON
4 Q104
ON
5 Q105
ON
6 Q106
ON
7 Q107
ON
8 Q108
ON
9 Q109
ON
10 Q110
ON
0...10 – 1
–
211 Input
test
(sensor test)
1
Sensor connected to B101
2
Sensor connected to B102
3
Sensor connected to B103
4
Sensor connected to B104
5
Sensor connected to B105
6
Sensor connected to B106
7
Sensor connected to B107
8
Sensor connected to B108
9
Sensor connected to B109
10
Room temperature sensor (PPS room unit)
11
Display of input H1 ( contact or DC 0…10 V)
12
Display of E1 (AC 230 V)
1...12 – 1
–
212 Display of PPS communication
Query with the + / - buttons
- - -
No communication
1...12
PPS device address
0...255 identification
code
--- / 1..12 /
0..255
– 1
–
Setpoint / actual value of the common flow
220 Display of the common flow temperature setpoint
--- No
value
available
0.0...140.0 °C
0.1 –
221 Actual value of the common flow temperature
--- No
value
available
0...140 °C 1 –
Flue gas temperature
222 Actual value B8 of the flue gas temperature
--- No
value
available
-50...350 °C 1 –
223 Display of maximum value B8 of the flue gas temperature
--- No
value
available
To reset the maximum value to the actual value, press the + / - buttons
simultaneously for 3 seconds.
-50...350 °C 1 0
224 Maximum limitation of the flue gas temperature
--.-
Function OFF
--.- / 0...350
°C
1
--.-
225 Switch-on temperature flue gas temperature sensor
function (ZuFu10)
0...350 °C 1 60
226 Switch-off temperature flue gas temperature sensor
function (ZuFu10)
0...350 °C 1 40
Oil- / gas-fired boiler
Setpoints / actual values
250 Display of the boiler temperature setpoint (TKw)
Internal or external PPS-BMU
--- No
value
available
0...140 °C 1 –
251 Actual value of the boiler temperature (TKx)
B2 or LPB or external PPS-BMU
--- No
value
available
-50...350 °C 1 –
252 Setpoint of minimum limitation of the return temperature
Line 280
EXP
...95
°C 1 8
253 Actual value of return temperature B7
--- No
value
available
-50...350 °C 1 –