4.214 Floor curing data
The floor curing function has a fixed profile according to which the rooms are heated to
allow curing. The current values of the floor curing function are displayed here. The
function itself is activated under setting 738.
Display
Unit
0...32
0...95
Weekday
°C
TVw Flow
temperature
setpoint
0
4
8
12
16
20
24
1
2
3
4
5
6
7
8
9 10
23
92
Z
5
3
Speed-controlled pump
4.215 Display of speed of heating circuit pump Q2
•
Visualization of speed of the heating circuit pump
The speed of the heating circuit pump (in %) will automatically be displayed on this op-
erating line.
Display
Unit
0...100 %
---
The heating circuit pump is not speed-controlled
4.216 Minimum speed of the heating circuit pump
•
Minimum limitation of speed of the heating circuit pump
The minimum speed of the heating circuit pump can be defined. It is thus possible to
negate the lowest pump speeds, which cannot be properly controlled.
Setting range
Unit
Factory setting
0…line 742
%
100
4.217 Maximum speed of the heating circuit pump
•
Maximum limitation of speed of the heating circuit pump
The maximum speed of the heating circuit pump can be defined. It is thus possible to
negate the highest pump speeds, if required.
Setting range
Unit
Factory setting
Line 741…100
%
100
Description
Setting
Display
Benefit
Description
Setting
Benefit
Description
Setting
Benefit
Description
Setting