317/348
Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the EXP settings 18.10.2002
5.60 Actuator running time heating circuit
•
Setting the actuator running time
Allows adjustments to be made to supplier-specific actuator running times.
Setting range
Unit
Factory setting
30...873 s
120
The actuator running time is the period of time the actuator requires to travel from one
end position to the other.
D.h.w. EXP
5.61 Maximum nominal setpoint of the d.h.w.
temperature (TBWmax)
•
Setting can be limited by the enduser
•
Reduced
risk
of
scalding
•
Minimized proneness to buildup of lime
Function for limiting the nominal setpoint of the d.h.w. temperature.
Setting range
Unit
Factory setting
8...80
°C 60
The setting will ensure maximum limitation of the nominal d.h.w. temperature setpoint
(setting 26).
0 10 20 30 40 50 60 70 80 90 100 120
130
140 °C
23
92
Z
32
26
Setting "Nominal setpoint of the d.h.w. temperature”
770
Setting "Reduced setpoint of the d.h.w. temperature”
750
EXP
Setting "Maximum nominal setpoint of the d.h.w. temperature”
Benefit
Description
Setting
Note
Benefit
Description
Setting
Effect