Description of the heating engineer settings
18.10.2002
Diagnosis
4.125 Functional test of the wood-fired boiler
•
Individual relays or combinations of relays can be controlled for test purposes
The functional test makes possible the control of individual relays or relay combinations
in order to check the functionality.
Setting range
Unit
Factory setting
--- / 0...4
–
- - -
To activate the required test step, press the + / - buttons:
--- No
test
0 Everything
OFF
1
Boiler pump ON (Q10)
2
In addition, release ON (Q10 + K3)
3
In addition, maintained boiler return temperature OFF (Q10 + K3 + Y10)
4
In addition, maintained boiler return temperature ON (Q10 + K3 + Y9)
With test steps 0, 1 and 2, the valve for the maintained boiler return temperature can be
in any position (passive, dead).
Heat pump
Setpoints / actual values
•
The settings on operating lines 400 through 404 are used for visualizing the plant
state.
4.126 Display of heat pump flow temperature
setpoint
The current heat pump flow temperature setpoint will automatically be displayed on this
operating line.
Display
Unit
0...140 °C
Benefit
Description
Setting
Effect
Note