Description of the EXP settings
18.10.2002
TK Boiler
temperature
TKx
Actual value of the boiler temperature
Tkmin Minimum limitation of the boiler temperature (operating line 270)
SDK
Switching differential of the boiler (factory setting = 8 K), operating line 252
EXP.
t Time
Y Locking
signal
5.11 Control of the boiler pump
•
Boiler pump control mode can be selected.
The setting defines the criteria according to which the boiler pump shall be operated.
Setting range
Unit
Factory setting
0 / 1
–
0
The settings have the following meaning:
0
The boiler pump operates when there is a demand for heat.
In that case, the boiler pump responds to locking signals.
1
The boiler pump operates when there is a demand for heat or when the burner
operates. In that case, the boiler pump does not respond to locking signals (pro-
tective boiler start-up).