Description of the heating engineer settings
18.10.2002
4.50 Input
test
•
Commissioning is facilitated
•
Wiring errors can be pinpointed very rapidly
The input test can be used for checking the wiring.
It is also termed sensor test.
Setting range
Unit
Factory setting
1...12 Increment
1
The input test will automatically become available on this operating line.
With each test step, the respective input will be displayed so that it can be checked. By
pressing the + / - buttons, it is possible to change from one test step to the next.
Display
The selected sensor values are updated within a maximum of 5 seconds.
The display is made with no measured value correction.
Benefit
Description
Setting
Effect
Test step 1
Test step 2
Test step 3
Test step 4
Test step 5
Test step 6
Test step 7
Test step 8
Test step 9
Test step 10
Test step 11
Test step 12
Display of input B101
Display of input B102
Display of input B103
Display of input B104
Display of input B105
Display of input B106
Display of input B107
Display of input B108
Display of input B109
Display of room (PPS room unit)
Display of input H1 according to the function selected on operating
line 870
(contact input: --- = contact open.
ooo = contact closed / 0-10V Input: temperature in °C
Display of input E1
(--- = no Signal, ooo = 230 V AC)