140/348
Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the heating engineer settings
18.10.2002
4.70 Functional test of oil- / gas-fired boiler
•
Individual relays or combinations of relays can be controlled for test purposes
To check the functionality, the functional test enables individual terminals or combina-
tions of terminals to be controlled.
Setting range
Unit
Factory setting
--- / 0...5
–
---
The following test steps are available (can be selected with the + / - buttons):
--- No
test
0 Everything
OFF
1
Boiler pump (Q1) ON
2
In addition, burner stage 1 ON (Q1 + K4)
3
In addition, burner stage 2 ON (Q1 + K4 + K5)
4
In addition, maintained boiler return temperature / bypass pump ON (Q1 + K4 +
K5 + Q12 / Y8)
5
Maintained boiler return temperature / bypass pump OFF (Q1 + K4 + K5 + Y7)
The functional test is only possible for internal heat sources.
With test steps 0…3, the mixing valve for the maintained boiler return temperature can
be in any position. The position of the mixing valve will only be defined with test steps 4
(ON) and 5 (OFF).
The functional test will be terminated when leaving the operating line.
Benefit
Description
Setting
Effect
Notes