314/348
Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the EXP settings
18.10.2002
5.55 Heat gains (Tf)
•
To save energy, heat gains are taken into consideration
This setting takes into account potential heat gains from machines, pieces of equip-
ment, or other constant heat sources, that might adversely affect accurate control. The
value will change when the heating curve adaption is activated.
Setting range
Unit
Factory setting
-2...+4 K
0
The setting compensates the sum of all constant heat gains as follows:
Increase:
For more compensation
In the case of significant heat sources
Decrease: For
less
compensation
In the case of less significant heat sources
The setting in K corresponds to the temperature differential that would result if the room
was solely heated by the heat gains.
5.56 Adaption sensitivity 1 (ZAF2)
•
Different heating curve adaptions as a function of the outside temperature
Adaption sensitivity 1 serves for calculating the heating curve adaption in the
temperature range
between
4...12 °C. Also refer to section “Adaption of heating curve”,
operating line 726.
Setting range
Unit
Factory setting
1...15 –
15
The level of adaption sensitivity is automatically adapted by the controller and, there-
fore, need not be manually adjusted.
The heating curve in the temperature range between 4 and 12 °C will be differently
adapted, depending on the level of adaption sensitivity 1.
Increase: More
adaption
Decrease: Less
adaption
Each time a significant adaption of the heating curve
between
4 and 12 °C (ZAF1) has
taken place, adaption sensitivity 1 will automatically be reduced by one step. This
means that the extent of adaption and thus the readjustment of the slope and the heat-
ing curve’s parallel displacement will gradually be reduced .
When readjusting the slope of the heating curve (operating line 30), the adaption sensi-
tivity will automatically be reset to the factory-set value.
Refer to the next section "Adaption sensitivity 2“.
For more detailed information about the effects, refer to operating line “Adaption of the
heating curve” (operating line 726).
Benefit
Description
Setting
Effect
Benefit
Description
Setting
Effect
Reduction
Note
Diagram
Note