Description of the heating engineer settings
18.10.2002
Floor curing
4.213 Floor curing
•
The floor curing function ensures controlled drying of the floor
The floor curing function maintains the flow temperature at a predefined temperature
profile with the help of the mixing valve.
Setting range
Unit
Factory setting
0...3 –
0
Selection of a temperature profile activates the floor curing function and the heating cir-
cuit ensures the preset flow temperatures.
0 Inactive
1 Functional
heating
2 Floor
curing
heating
3
Functional and floor curing heating
4.213.1 Temperature profile
The following graph shows the temperature profile of the selected floor curing function.
50
45
40
35
30
20
5
10
15
18
[Tag]
0
25
TVmax
Fh
Bh
1
1
5
7
X
Fh + Bh
1
25
23
73
Z
59
[TVw]
TVw Flow
temperature
setpoint
x Start
day
Fh Functional
heating
Bh Floor
curing
heating
Benefit
Description
Setting
Effect