115/348
Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the heating engineer settings
18.10.2002
Buffer storage tank cooling via the heat source pump is no longer possible when using
the heat generation lock (the heat source has no access to the buffer storage tank).
Also, frost protection for the buffer storage tank is no longer ensured by the oil- / gas-
fired boiler. If frost protection for the buffer storage tank is required, an electric immer-
sion heater (ZuFu 24) must be used.
The automatic heat generation lock can be integrated in the diagram as follows:
Example:
23
93
Z1
6
B2
Q1
K4
OeG 1
B4
B41
Sp 2
ZuFu 27
1
0
Y4 (Y 4)
B6
Sol 3
Q5
K9
B62
0
1
Notes
Application example