32/348
Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Handling
18.10.2002
Line Function
Range
Unit
Resolution Factory
setting
39
Resetting the heating circuit and d.h.w. time switch
programs
To set the time switch programs to their default values, press the
+ / - buttons simultaneously for 3 seconds.
0 / 1
–
1
0
Holiday program
40
Preselection of holiday period
1...8
–
1
1
41
Beginning of holiday period
--.-- Inactive
To cancel the selected holiday period, press the + / - buttons si-
multaneously for 3 seconds.
--.-- / 01.01...31.12 Weekday /
month
1 day
--.--
42
End of holiday period
--.-- Inactive
To cancel the selected holiday period, press the + / - buttons si-
multaneously for 3 seconds.
--.-- / 01.01...31.12 Weekday /
month
1 day
--.--
General / service
50
Indication of errors
0..255 /
00.01...14.16
– 1
–
Oil-/ gas-fired boiler
60 Chimney
sweep
0 = OFF
1 = ON
Outside the programming level, the second burner stage can be
switched on and off with the + / - buttons.
0 / 1
–
1
0
Solar collectors
65
24-hour yield of solar energy
0...999.9
kWh
0.1
0
66
Total yield of solar energy
To reset the total yield to 0, press the + / - buttons simultaneously
for 3 seconds.
0...9999999.9 kWh 0.1 0
Heat pump
75
Acknowledgement of heat pump error messages 135
and 137
To reset error messages 135 and 137, press the + / - buttons si-
multaneously for 3 seconds.
0 / 1
–
1
0