Description of the EXP settings
18.10.2002
5.51 Boost of room temperature setpoint
•
Reduction of the room’s heating up time
Boosts the room temperature setpoint temporarily, aimed at achieving shorter heating
up times for the room. This setting is active only if a room temperature sensor is used.
Setting range
Unit
Factory setting
0...20 K
5
The duration of boost heating will be changed.
Entry:
Increase:
More setpoint boost
Heating up time will become shorter
Decrease: Less
setpoint
boost
Heating up time will become longer
Boost heating is started as soon as switching to a higher room temperature setpoint
occurs (e.g. switching times in automatic mode).
The room temperature setpoint will be raised by the setting made on line 703
EXP
until
the room is heated up (TRw - ¼ °C).
The boost produces an increase in the flow temperature setpoint.
20
15
°C
t
TR
w
TR
x
23
92
D01
a
b
TRN
TRR
TRx Actual value of the room temperature
TRw Room temperature setpoint
TRN Nominal room temperature setpoint
TRR Reduced room temperature setpoint
703
EXP
Boost of room temperature setpoint
t Time
Benefit
Note
Setting
Effect
Boost heating