Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Handling
18.10.2002
2.5.1 Overview of enduser parameters
Line Function
Range
Unit
Resolution Factory
setting
Setting the clock
1
Time of day
00:00...23:59
h / min
1 min
–
2 Weekday
1...7
Weekday 1
day –
3
Date
01.01...31.12
Day / Month
1 day
–
4 Year
2001...2094
Year
1
Year –
Time switch program for heating circuit
5 Weekday-preselection
heating
circuit
1-7 7-day
block
1...7 Individual
days
1-7 / 1...7
Weekday
1 day
–
6
Switch-on time
1. period heating circuit
00:00...24:00
h / min
10 min
06:00
7
Switch-off time
1. period heating circuit
00:00...24:00
h / min
10 min
22:00
8
Switch-on time
2. period heating circuit
00:00...24:00
h / min
10 min
- -:- -
9
Switch-off time
2. period heating circuit
00:00...24:00
h / min
10 min
- -:- -
10
Switch-on time
3. period heating circuit
00:00...24:00
h / min
10 min
- -:- -
11
Switch-off time
3. period heating circuit
00:00...24:00
h / min
10 min
- -:- -
Free time switch program
12
Weekday preselection of free time switch program 1
1-7 7-day
block
1...7 Individual
days
1-7 / 1...7
Weekday
1 day
–
13
Switch-on time 1. phase of free time switch progr.
00:00...24:00
h / min
10 min
06:00
14
Switch-off time 1. phase of free time switch progr.
00:00...24:00
h / min
10 min
22:00
15
Switch-on time 2. phase of free time switch progr.
00:00...24:00
h / min
10 min
- -:- -
16
Switch-off time 2. phase of free time switch progr.
00:00...24:00
h / min
10 min
- -:- -
17
Switch-on time 3. phase of free time switch progr.
00:00...24:00
h / min
10 min
- -:- -
18
Switch-off time 3. phase of free time switch progr.
00:00...24:00
h / min
10 min
- -:- -
Time switch program for d.h.w. heating
19
Preselection of weekday
1-7 7-day
block
1...7 Individual
days
1-7 / 1...7
Weekday
1 day
–
20
Switch-on time
1. period d.h.w.
00:00...24:00
h / min
10 min
06:00
21
Switch-off time
1. period d.h.w.
00:00...24:00
h / min
10 min
22:00
22
Switch-on time
2. period d.h.w.
00:00...24:00
h / min
10 min
- -:- -
23
Switch-off time
2. period d.h.w.
00:00...24:00
h / min
10 min
- -:- -
24
Switch-on time
3. period d.h.w.
00:00...24:00
h / min
10 min
- -:- -
25
Switch-off time
3. period d.h.w.
00:00...24:00
h / min
10 min
- -:- -
D.h.w. values
26
Nominal setpoint of the d.h.w. temperature (TBWw)
TBWR Line
770
TBWmax Line
750
EXP
TBWR...TBWmax °C
1
55
Heating circuit values
27
Reduced room temperature setpoint (TRRw)
TRF Line
28
TRN Setpoint
knob
TRF...TRN °C 0,5
16
28
Frost protection setpoint of the room temp. (TRFw)
TRR Line
27
4...TRR °C 0,5
10
29
Summer / winter changeover temperature
8...30
°C
0,5
17
30 Heating
curve
slope
1.0...40
–
0,2
15
33
Actual value of the room temperature (TRx)
0...50
°C
0,5
–
General
34
Actual value of the outside temperature (TAx)
To set the attenuated outside temperature to TAx, press the + / -
buttons simultaneously for 3 seconds.
-50...+50 °C 0,5
–
38
Resetting the enduser parameters
To reset the parameters of the enduser level to their default values,
press the + / - buttons simultaneously for 3 seconds.
0 / 1
–
1
0