CE1P2488en
HVAC Products
Description of the heating engineer settings
18.10.2002
General functions
4.241 Effect of the green button
•
Effect of the green button can be selected
The impact of the green button on the heating circuits and / or on the d.h.w. depends
on the selection made here.
Setting range
Unit
Factory setting
1...3 –
2
When pressing the green button, the heat sources operating on nonrenewable forms of
energy (oil / gas / heat pump / electric immersion heaters) will be locked. The demand
for heat received from the heating circuits and / or d.h.w. will no longer be considered.
Any comfort losses with regard to the d.h.w. and / or the heating circuits will be accepted.
The operating line makes it possible to define the demand for heat that shall be ig-
nored:
1 D.h.w.
Demand for heat from d.h.w. will be ignored by the above mentioned heat sources.
The d.h.w. will only be heated by heat delivered by a wood-fired boiler or by solar
collectors.
2 Heating
circuit
Demand for heat from the heating circuit will be ignored by the above mentioned
heat sources. The heating circuits will only be heated by heat delivered by a wood-
fired boiler or by solar collectors.
3
D.h.w. and heating circuit
Demand for heat from d.h.w. and the heating circuits will be ignored by the above
mentioned heat sources. All the heat required by the plant is delivered by a wood-
fired boiler or by solar collectors.
Ignoring the demand for heat from d.h.w. is possible only if the d.h.w. is controlled by
the RVP540 / RVP550. In the case of an external demand for heat, no differentiation is
made between d.h.w. and heating circuit.
4.242 Frost protection for the plant with the system
pump
“Frost protection for the plant with the system pump” can be switched on and off.
Setting range
Unit
Factory setting
0 / 1
–
1
0
The “General frost protection for the plant“
does not act
on the system pump.
1
The “General frost protection for the plant“
acts
on the system pump.
If the “General frost protection for the plant” (operating line 180
EXP
) is switched off, the
setting made on this operating line (803) has no impact.
A detailed description of the impact of frost protection for the plant is given on operating
line 180
EXP
.
Benefit
Description
Setting
Effect
Notes
Description
Setting
Effect
Notes