Description of the heating engineer settings
18.10.2002
Release depending on the outside temperature
Parameters 630 through 632 limit the outside temperature range in which the individual
heat sources (oil / gas, heat pump, controllable wood-fired boiler) are released. It is
thus possible to select whether bivalent operation shall take place alternatively, parallel
or partial-parallel.
The example shows the interrelationship of operating lines 630 through 632.
In the hatched outside temperature range, the relevant heat source is released.
20
10
0
-10
-20
30
°C
23
92
Z
55
TAx
ged
OeG
Ho
Wp
SD
SD
SD
-30
Wp heat
pump
Ho wood-fired
boiler
OeG
Oil- / gas-fired boiler
630
Release of the oil- / gas-fired boiler below the outside temperature threshold
631
Release of the heat pump above the outside temperature threshold
632
Release of the wood-fired boiler below the outside temperature threshold
SD
Switching differential for switch-on / off outside temperature is fixed at 1 K
TAx
ged
Composite outside temperature (operating line 705)
20
10
0
-10
-20
30
°C
23
92
Z60
TAx
gem
OeG
Wp
-30
SD
SD
20
10
0
-10
-20
30
°C
23
92
Z
62
TAx
ged
OeG
Wp
SD
SD
-30
Description
Interrelationship
of settings
Examples:
Bivalent-alternative
Bivalent-partially-parallel