198/348
Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the heating engineer settings
18.10.2002
4.165 Priority of buffer storage tank cooling with
the heat source pump
The priority of the cooling function can be selected (OFF / priority 1 / priority 2).
When the selected priority is released, the heat will be delivered to the boiler by acti-
vating the heat source pump (Q1 and / or Q10). If a mixing valve for maintained boiler
return temperature is used, it will be brought to the through-port position.
This kind of cooling works only if permitted by the selected type of hydraulic circuit.
Setting range
Unit
Factory setting
--- / 1...2
–
1
The cooling function will be stopped as soon as the selected priority is no longer re-
leased (refer to mode of operation on page 195).
4.166 Priority of buffer storage tank cooling with
overtemperature protection output K11
The priority of the cooling function can be selected (OFF / priority 1 / priority 2).
Relay K11 will be energized as soon as the selected priority is released.
This allows an external heat consumer (e.g. a swimming pool) to be activated.
Setting range
Unit
Factory setting
--- / 1...2
–
1
The cooling function will be stopped (relay K11 will be deenergized) as soon as the se-
lected priority is no longer released (refer to “Functioning” on page 195).
Description
Note
Setting
Effect
Description
Setting
Effect