Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the enduser settings
18.10.2002
General
3.22 Actual value of the outside temperature
The actual value of the outside temperature will automatically be displayed on this op-
erating line.
Display
Unit
- 50.0 ... + 50.0
°C
– – –
Sensor with open-circuit or no sensor connected
On this operating line, it is also possible to reset the attenuated outside temperature
(operating line 704). To do this, press the + / - buttons simultaneously for 3 seconds. As
soon as the display stops flashing, the attenuated outside temperature is reset to the
actual outside temperature.
3.23 Resetting the enduser parameters
The parameters of the ”Enduser” level can be commonly reset. To do this, press the + /
- buttons simultaneously for 3 seconds.
Setting range
Unit
Factory setting
0 / 1
-
0
All parameters of the ”Enduser” level – with the exception of the time switch programs –
will be reset to their default values.
The time switch programs are reset on the next operating line.
3.24 Resetting the heating circuit and d.h.w. time
switch programs
•
Straightforward resetting of all time switch programs to their standard values
The standard time program represents a reset of the time settings of the heating circuit
and d.h.w. time switch programs. For this purpose, the controller is supplied with non-
volatile factory settings.
1. Press the operating line selection buttons to select line 39.
2. Press the + / - buttons simultaneously for 3 seconds.
The standard time program is activated as soon as the display changes to 1.
Display
Unit
0 / 1
-
In that case, the individual settings will be lost!
Description
Setting
Special displays
Resetting
Description
Setting
Effect
Benefit
Description
Setting
Caution