4.237 Setpoint of the legionella function
•
Adjustable temperature level to kill legionella bacteria
The setpoint of the legionella function is an adjustable temperature level to which the
d.h.w. temperature is raised when the legionella function is activated. For details, also
refer to "Legionella function", operating line 790.
Setting range
Unit
Factory setting
60...95 °C
65
The setting changes the d.h.w. setpoint during the period of time the d.h.w. is heated
up as a result of the legionella function.
To ensure effective killing of the legionella bacteria, the setpoint of the legionella func-
tion must be adjusted to a minimum of 60 °C. Too high temperatures (above approxi-
mately 70 °C) do not offer any additional benefit but only lead to the formation of scale
in the storage tank.
4.238 Time for the legionella function
•
The time for the legionella function can be adjusted
The legionella function will be triggered during the selected period (operating line 790)
at the time of day set here.
Setting range
Unit
Factory setting
00:00...24:00 hh:mm
18:00
4.239 Dwelling time at legionella function setpoint
•
Adjustable minimum dwelling time at the legionella setpoint
The setpoint of the legionella function (operating line 792) is maintained for at least the
period of time set here.
Setting range
Unit
Factory setting
--- / 10...360
min
30
---
Function deactivated (no dwelling time)
The dwelling time starts as soon as the legionella setpoint is reached. During the entire
dwelling time, the temperature may not fall below the legionella setpoint by more than
the d.h.w. switching differential (operating line 751
EXP
, standard setting 5 K) + 2 K. The
legionella function is terminated when this criterion is met.
If the legionella function cannot be performed within 40 hours since it was last triggered
(temperature not in the desired range during the entire dwelling time), operating line 50
will display an error message and the legionella function will be repeated at the next
time set (see operating lines 790 and 791).