Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the heating engineer settings
18.10.2002
Functions
4.148 Buffer storage tank charging with the wood-
fired boiler
•
Buffer storage tank charging with one or 2 sensors
Depending on the setting chosen, the buffer storage tank can be charged with only one
sensor (at the top) or with 2 sensors (top and bottom).
Setting range
Unit
Factory setting
0 / 1
–
0
Entry:
0
The buffer storage tank is charged with the help of sensor B4 and a switching
differential.
As soon as the temperature at sensor B4 drops 2 K below the required value,
the buffer storage tank will be charged until the temperature at sensor B4 lies
one switching differential above the temperature displayed on operating line
456 (slave pointer).
1
The buffer storage tank is charged with the help of sensors B4 and B41/B42
(start / stop behavior).
If B4 (top) drops 2 K below the required temperature, the buffer storage tank
will be charged until the temperature at sensor B41 (bottom) reaches the tem-
perature displayed on operating line 456 (slave pointer).