Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the heating engineer settings
18.10.2002
4.23 System pump Q14 (ZuFu6)
•
Location and type of activation of the system pump can be selected
The system pump can be located before or after the d.h.w. storage tank or it can be
defined as a system pump for external consumers. The required function is to be se-
lected on operating line 195.
Setting range
Unit
Factory setting
--- / 101...110
Q14
---
The auxiliary function is activated as soon as system pump
Q14
is assigned to a free
terminal.
101...110
System pump Q14 can be assigned to a free relay terminal between
Q101 and Q110.
---
No assignment made and the system pump is not activated.
The system pump can be integrated in the diagram as follows:
Example of integration before / after the d.h.w. storage tank
Q14
ZuFu 6
B3
B31
BwSp 3
Q3
Q14
ZuFu 6
B3
B31
BwSp 3
Q3
23
93
Z
0
6
B9
Y1/Y2
Q2
B1
Rh 3
A6
Benefit
Description
Setting
Assignment
Application example