124/348
Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the heating engineer settings
18.10.2002
4.46 Display of sensor terminal assignment
•
Visualization of sensor terminal assignment
The assignment of the sensors to the controller terminals can be queried via the oper-
ating line.
Display
Unit
b 1…99 / 101…109
–
This operating line shows the assignment of the controller terminals to the relevant
sensors. By pressing the + / – buttons, the assignment of all terminals can be called up.
With every press of the button, the display changes to the next higher or next lower
terminal.
The first 3 digits correspond to the sensor shown in the diagram.
b1...b99
Corresponds to the sensor number shown in the diagram.
To make certain there will be no confusion with number 8, the display shows a
lower case (b).
The second 3 digits corresponds to the sensor terminal at the rear of the controller.
101...109
Corresponds to terminal number B101…B109 to which the previously
displayed sensor is assigned.
Example of assigning sensor B41 to terminal B102:
0
4
8
12
16
20
24
1
2
3
4
5
6
7
8
9 10
23
92
Z
3
5
The display of - - - means that the relevant terminal is not used.