Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the heating engineer settings
18.10.2002
4.183 Priority of d.h.w. storage tank cooling with
overtemperature protection output K11
The priority of the cooling function can be selected (OFF / priority 1 / priority 2).
Relay K11 will be energized as soon as the selected priority is released.
This allows an external heat consumer (e.g. a swimming pool) to be activated.
Setting range
Unit
Factory setting
--- / 1...2
–
1
The cooling function will be stopped as soon as the selected priority is no longer re-
leased (refer to “Functioning” on page 206).
Diagnosis
4.184 Functional test of the d.h.w. storage tank
•
Individual relays or combinations of relays can be controlled for test purposes
The functional test makes possible the control of individual relays or relay combinations
in order to check the functionality.
Setting range
Unit
Factory setting
--- / 0...3
–
–
Press the + / – buttons to activate the required test step:
--- No
test
0 Everything
OFF
1
Charging pump ON (Q3)
2
In addition, diverting valve ON (Q3 + Y3)
3
Transfer pump ON (Q13)
Combi storage tanks
4.185 B4 delivers the temperature signal for the
B31 functionality
•
Saving a sensor
In small combi storage tanks, sensors B4 and B31 may be very close together and de-
liver nearly identical temperature signals. In that case, it is possible to define that sen-
sor B4 delivers the value for the functions that normally use the value of sensor B31.
Sensor B31 can thus be saved and must therefore be hidden (operating line 132).
Setting range
Unit
Factory setting
0 / 1
–
0
0 No
Sensor B31 is used for the functionality of B31.
1 Yes
Sensor B31 is used for the functionality of B4.
Description
Setting
Effect
Benefit
Description
Setting
Effect
Benefit
Description
Setting
Effect