CE1P2488en
HVAC Products
Description of the heating engineer settings
18.10.2002
4.204 Minimum limitation of the flow temperature
setpoint (TVmin)
•
Prevents too low flow temperatures
Minimum and maximum limitation define the range within which the flow temperature
setpoint may vary.
Setting range
Unit
Factory setting
8...TVmax °C
8
TVmax
Maximum limitation of the flow temperature setpoint (setting on operating line 724)
0 10 20 30 40 50 60 70 80 90 100
TV
max
min
akt
°C
2392
Z
28
TVw
TVw Current flow temperature setpoint
723 Minimum limitation of the flow temperature setpoint
724 Maximum limitation of the flow temperature setpoint
The setting will make certain that the flow temperature setpoint will not fall below a
minimum level.
If the flow temperature setpoint demanded by the heating circuit reaches the minimum
limit and the outside temperature rises, the flow temperature setpoint will be maintained
at that limit, in other words, it will not be allowed to fall below it. This may lead to exces-
sive room temperatures.
Benefit
Description
Setting
Effect
Limitation