Handling
18.10.2002
Line Function
Range
Unit
Resolution Factory
setting
Burner hours run counter / start counter
256 Burner operating hours stage 1 or PPS-BMU
Output K4 or PPS
(to reset to 0, press the + / - buttons simultaneously for 3 seconds)
0...999‘999 h
1
0
257 Burner operating hours stage 2
Output K5
(to reset to 0, press the + / - buttons simultaneously for 3 seconds)
0...999‘999 h
1
0
258 Number of burner starts stage 1
Output K4
(to reset to 0, press the + / - buttons simultaneously for 3 seconds)
0...999‘999 –
1
0
259 Number of burner starts stage 2
Output K5
(to reset to 0, press the + / - buttons simultaneously for 3 seconds)
0...999‘999 –
1
0
Functions
270 Minimum limitation of the boiler temperature (TKmin)
250
EXP
...251
EXP
(max. 95°C)
°C 1 40
271 Frost protection for the plant with the boiler pump
0
General frost protection for the plant does not act on this pump
1
General frost protection for the plant acts on this pump
0 / 1
–
1
1
Diagnosis
295 Indication of BMU error code
0...255
–
1
–
296 Functional test oil- / gas-fired boiler
--- No
test
0 Everything
OFF
1
Boiler pump ON (Q1)
2
In addition, burner stage 1 ON (Q1 + K4)
3
In addition, burner stage 2 ON (Q1 + K4 + K5)
4
Maintained boiler return temperature fixed ON
(Q1+K4+K5+Q12/Y7)
5
Maintained boiler return temperature fixed OFF
(Q1+K4+K5+Q12+Y8)
--- / 0...5
–
–
- - -
Solar collectors
Setpoints / actual values
300 Actual value of the collector temperature (B6)
--- No
value
available
-50...350 °C 1 –
301 Actual value of the collector temperature (B61)
--- No
value
available
-50...350 °C 1 –
302 Actual value of the collector flow temperature (B62)
--- No
value
available
-50...350 °C 1 –
303 Maximum value of collector temperature 1 (B6)
To reset to the actual value, press the + / - buttons simultaneously for
3 seconds
-50...350 °C 1 0
304 Maximum value of collector temperature 2 (B61)
To reset the actual value, press the + / - buttons simultaneously for
3 seconds
-50...350 °C 1 0
Temperature differentials collector / heat exchanger
305 Display of temperature differential collector 1 / heat ex-
changer 1
--- No
value
available
-50...350 K
1 –
306 Display of temperature differential collector 1 / heat ex-
changer 2
--- No
value
available
-50...350 K
1 –
307 Display of temperature differential collector 2 / heat ex-
changer 1
--- No
value
available
-50...350 K
1 –
308 Display of temperature differential 2 / heat exchanger 2
--- No
value
available
-50...350 K
1 –
309 Temperature differential collector 1 / swimming pool
--- No
value
available
-50...350 K
1 1
310 Temperature differential collector 2 / swimming pool
--- No
value
available
-50...350 K
1 1