Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the heating engineer settings
18.10.2002
Speed-controlled pump of wood-fired boiler
4.122 Display of speed of pump Q10 of the wood-
fired boiler
•
Visualization of speed of pump Q10 of the wood-fired boiler
The speed of the pump of the wood-fired boiler will automatically be displayed on this
operating line as a percentage figure.
Display
Unit
0...100 %
---
Heating circuit pump is not speed-controlled.
4.123 Minimum speed of pump of the wood-fired
boiler
•
Minimum speed limitation of boiler pump Q10
The minimum boiler pump speed can be defined. It is thus possible to negate the low-
est pump speeds, which cannot be properly controlled.
Setting range
Unit
Factory setting
0…max %
40
max Boiler pump, maximum speed of pump, operating line 392
4.124 Maximum speed of pump of the wood-fired
boiler
•
Maximum speed limitation of boiler pump Q10
The maximum boiler pump speed can be defined. It is thus possible to negate the high-
est pump speeds, if required.
Setting range
Unit
Factory setting
min…100 %
100
min
Boiler pump, minimum speed of the pump, operating line 391