Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the enduser settings
18.10.2002
3.3 Nominal room temperature setpoint
•
Straightforward setting of the required nominal room temperature setpoint
The heating system uses 3 different setpoints that can be adjusted:
•
The nominal room temperature setpoint described here
•
The reduced room temperature setpoint (setting on operating line 27)
•
The frost protection setpoint of the room temperature (setting on operating line 28)
The nominal room temperature setpoint is pre-adjusted with the setpoint knob. It is lo-
cated on the controller front for direct access by the user.
Setting range
Unit
Factory setting
8...26 °C
20
0 2 4 6 8 10 12 14 16 18 20 22 24 26
°C
2392Z45
Room temperature setpoint setting ranges
27
Setting: ”Reduced room temperature setpoint”
28
Setting: ”Frost protection setpoint of room temperature”
When the nominal room temperature setpoint is active, the rooms will be heated ac-
cording to the adjustment made with the setpoint knob.
Effect in the various operating modes:
Operating mode
Effect of knob adjustment
Adjustment
acts on the heating periods
Adjustment acts continuously
Adjustment has no effect
The adjustment made with the setpoint knob has priority over the reduced room tem-
perature setpoint entered (operating line 27). Especially in situations where the adjust-
ment made with the knob is lower.
0 2 4 6 8 10 12 14
16
18
20
22
24 h
...
237
3Z
11
Mo
Su
During the heating periods, the nominal room temperature setpoint is maintained. The
heating periods are in accordance with the time switch program.
Benefit
Description
Setting
Effect of temperature
setting
Note
Example