12.2 Compliance with EN Directives
12-5
1
2
A
pp
endix
12.2.3 Precautions for noise filter connection
Precautions for noise filter mounting and wiring
See below precautions for mounting and wiring when noise filter is used.
■
Do not bundle with input line and output line of noise filter. (Earth line also.)
Avoid that go through a same duct. (It might reduce effect of filter, and noise might come
around through that point.)
■
Each of earth line shall be connected to grounding plate in a control panel by single-point.
Also in case of multi axes construction in same control panel, grounding by single-point.
NG
Noise filter
Noise filter
Input
Output
Input
Output
Servo amplifier
Servo motor
Noise filter
Encoder cable
AC 200V
Control panel
Servo motor power cable
3 phase/ single
phase
Grounding plate
(Place it in the control panel)
Summary of Contents for Sanmotion R 3E S