8.3 Trouble shooting when alarm activated
8-18
8
Maintenance
■
Alarm Code 55 (External Error)
When host device or thermal output signal of external regenerative resistor are not connected
Corrective
actions
When thermal signal of the external regenerative resistor is connected
Corrective
actions
* When output terminal of upper level device is connected, eliminate the alarm trigger of the host
level device.
Status at the time of alarm
Cause
1
2
Issued when control power is turned ON.
✔
✔
Cause
Investigation and corrective actions
1
■
Validity condition for external trip
function is set to
‘
Valid
’
.
■
When not used, set
"00:_Always_Disable” at Group9
ID40 "External Trip Input Function
[EXT-E]".
2
■
Defect in internal circuit of servo
amplifier.
■
Replace the servo amplifier.
Status at the time of alarm
Cause
1
2
3
Issued when control power is turned ON.
✔
✔
Issued after operation for some time.
✔
✔
Cause
Investigation and corrective actions
1
■
Improper wiring of external
regenerative resistance.
■
Check the wiring conditions and
correct it if improper.
2
■
External regenerative resistor is
operating.
■
Check the operating conditions.
■
Increase the capacity of the
external regeneration resistor.
3
■
Defect in internal circuit of servo
amplifier.
■
Replace the servo amplifier.
Summary of Contents for Sanmotion R 3E S
Page 1: ...M0010630G For Rotary Motor Instruction Manual Analog Pulse Input Type ...
Page 2: ......
Page 76: ...No Text on This Page ...
Page 88: ...No Text on This Page ...
Page 266: ...No Text on This Page ...
Page 332: ...No Text on This Page ...
Page 408: ...No Text on This Page ...
Page 444: ...No Text on This Page ...
Page 511: ...12 7 Optional parts dimensions 12 65 12 Appendix REGIST 1000W Wiring diagram ...
Page 512: ...No Text on This Page ...