5. Operation
5-57
-
Group1
-
ID
Contents
01
Position Command Filter
[PCFIL]
Setting range
Unit
Default
0.0 to 2000.0
ms
0.0
■
This primary low-pass filter suppresses any sudden change of the position control pulse.
Sets time constants.
This parameter setting is valid when the value of Group1 ID08 Higher Tracking Control
Position Compensation Gain is set at 0%.
When Higher Tracking Control Position Compensation Gain is 0%, and this value is set
at 0.0ms, the filter becomes invalid.
This filter can suppress overshoot caused by the rise of the feed forward compensation
gain.
02
Position Loop Proportional Gain 1
[KP1]
Setting range
Unit
Default
1 to 3000
1/s
30
■
Proportional gain for position controller.
Automatically overwrite by Auto-tuning result saving.
When Auto-tuning function is valid, this setting value is not applied.
When Gain switching function is valid, this setting value is applied by selecting gain 1.
When Gain switching function is invalid, this setting value is applied.
03
Position Loop Integral Time Constant 1
[TPI1]
Setting range
Unit
Default
0.3 to 1000.0
ms
1000.0
■
Integral time constant for position controller.
This setting is valid when the Position Loop Proportional Control Switching Function is invalid.
Integral term is invalid (proportional control) at the setting value 1000.0ms.
When Gain switching function is valid, this setting value is applied by selecting gain 1.
When Gain switching function is invalid, this setting value is applied.
04
Position loop phase lead compensation gain
[PLPHLK]
Setting range
Unit
Default
0 to 100
%
0
■
Sets the phase improving value of Position loop phase lead compensation.
For position loop, adds the function that shifts phase on phase lead compensation
frequency (PLPHLF) as 17deg by 50% and 35deg by 100%. Pay attention for gain
increment after PLPHLF.
This parameter will be disabled when 0% is set.
05
Position loop phase lead compensation frequency
[PLPHLF]
Setting range
Unit
Default
10 to 4000
Hz
500
■
Sets the frequency that is wanted to improve the phase of position loop.
Set value will limit 1,000Hz even if 1,000Hz or more is set.
This parameter can set in 1 Hz unit, but it will be rounded down to the 10 Hz internally.
✔
Please stop servo motor if change this value.
PCFIL [ms]
63.2%
36.8%
PCFIL [ms]
Summary of Contents for Sanmotion R 3E S
Page 1: ...M0010630G For Rotary Motor Instruction Manual Analog Pulse Input Type ...
Page 2: ......
Page 76: ...No Text on This Page ...
Page 88: ...No Text on This Page ...
Page 266: ...No Text on This Page ...
Page 332: ...No Text on This Page ...
Page 408: ...No Text on This Page ...
Page 444: ...No Text on This Page ...
Page 511: ...12 7 Optional parts dimensions 12 65 12 Appendix REGIST 1000W Wiring diagram ...
Page 512: ...No Text on This Page ...