5. Operation
5-111
-
Group9
-
ID
Contents
27
Velocity loop proportional control switching function
[VLPCON]
■
You can switch between velocity loop PI control and P control.
Enabling velocity loop proportional control switching function (VLPCON) enables
switching.
Allocating conditions to enable velocity loop proportional control switching function.
When VLPCON signal is enabled, the control is switched to proportional control.
PI control (proportional
・
integral control)
・・
Velocity loop proportional gain
(KVP)/ integral time constant (TVI)
P control (proportional control)
・・・・・・
Velocity loop proportional gain (KVP)
✔
Switching to proportional control decreases servo gain, and servo system becomes
easy to stable.
✔
In the default setting, the velocity loop integral time constant (TVI) is 1000.0ms, so the
integral function is invalid.
Automatically overwrite by Auto-tuning result saving.
When Auto-tuning function is valid, this setting value is not applied.
34
Stick-slip behavior compensation function
[STC]
■
This enables stick motion compensation function in quadrant to compensate trajectory error
occurred due to quadrant switching, for use in applications for arc-shape or curved surface
process, such as NC machining equipments.
The conditions for enabling compensatory function for stick-slip behavior are assigned.
The compensatory function for stick-slip behavior becomes enabled If the STC signal is
valid.
35
Minor vibration suppression function
[FBHYST]
■
Minor vibration suppression function to suppress mechanical system-induced vibration caused
by encoder pulse modulation is enabled when motor stops.
The conditions for enabling minor vibration suppression function are assigned. The
minor vibration suppression function becomes enabled If the FBHYST signal is valid.
40
External trip input function
[EXT-E]
■
Contact input such as external thermal device can be taken in servo amplifier, and then output as
an alarm (AL.55).
Allocating conditions to enable external trip function. When EXT-E signal is enabled, this
becomes alarm (AL.55).
41
Emergency stop function
[EMR]
■
This can urgently stop servo motor by taking unit emergency signal into servo amplifier.
Allocating conditions to enable unit emergency signal. When EMR signal is enabled,
motor urgently stops.
Summary of Contents for Sanmotion R 3E S
Page 1: ...M0010630G For Rotary Motor Instruction Manual Analog Pulse Input Type ...
Page 2: ......
Page 76: ...No Text on This Page ...
Page 88: ...No Text on This Page ...
Page 266: ...No Text on This Page ...
Page 332: ...No Text on This Page ...
Page 408: ...No Text on This Page ...
Page 444: ...No Text on This Page ...
Page 511: ...12 7 Optional parts dimensions 12 65 12 Appendix REGIST 1000W Wiring diagram ...
Page 512: ...No Text on This Page ...