874
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
This parameter sets the quantity of reference for the function set for terminal A1 as a percentage when 10 V (or 20
mA) is input.
Use this parameter and
H3-04 [Terminal A1 Bias Setting]
to adjust the characteristics of the analog input signal to
terminal A1.
■
H3-04: Terminal A1 Bias Setting
No.
(Hex.)
Name
Description
Default
(Range)
H3-04
(0412)
RUN
Terminal A1 Bias Setting
Sets the bias of the analog signal input to MFAI terminal A1.
0.0%
(-999.9 - +999.9%)
This parameter sets the bias for the function set for terminal A1 as a percentage when 0 V (4 mA or 0 mA) is input.
Use this parameter and
H3-03 [Terminal A1 Gain Setting]
to adjust the characteristics of the analog input signal to
terminal A1.
■
H3-05: Terminal A3 Signal Level Select
No.
(Hex.)
Name
Description
Default
(Range)
H3-05
(0413)
Terminal A3 Signal Level
Select
Sets the input signal level for MFAI terminal A3.
0
(0 - 3)
0 : 0-10V (LowLim=0)
The voltage signal is 0 Vdc to 10 Vdc. The minimum input level limit is 0%. The drive will read a negative input
signal caused by gain and bias settings as 0%.
1 : -10 to +10V (Bipolar Reference)
The voltage signal is -10 Vdc to 10 Vdc. This setting enables positive and negative polarity signals. When the drive
uses this setting as the frequency reference, a Forward Run command will run the motor in reverse and a Reverse Run
command will run the motor forward. The gain and bias settings will cause the signal to be a negative number.
2 : 4 to 20 mA
The current signal is 4 mA to 20 mA. The minimum input level limit is 0%. The drive will read a negative input
signal caused by gain and bias settings as 0%.
3 : 0 to 20 mA
The current signal is 0 mA to 20 mA. The minimum input level limit is 0%. The drive will read a negative input
signal caused by gain and bias settings as 0%.
Note:
When
H3-05 = 0, 1
, set DIP switch S1-3 to the V side (voltage). When
H3-05 = 2, 3
, set DIP switch S1-3 to the I side (current). The default
setting is the V side (voltage).
■
H3-06: Terminal A3 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
H3-06
(0414)
Terminal A3 Function
Selection
Sets the function for MFAI terminal A3.
2
(0 - 32)
Note:
When terminal A3 is the PTC input terminal:
•
Set H3-06 = E [Motor Temperature (PTC input)]
•
Set DIP switch S4 to the PTC side
•
Set DIP switch S1-3 to the V side
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...