YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
929
Note:
You can disable Auto Restart for faults if you must not restart the machine after the fault.
Table 12.69 List of Faults during which Auto Restart is Available
Fault
Name
Parameters to Disable
Auto Restart
GF
Ground Fault
L5-08
LF
Output Phase Loss
-
oC
Overcurrent
-
oH1
Heatsink Overheat
L5-08
oL1
Motor Overload
L5-07
oL2
Drive Overload
L5-07
oL3
Overtorque Detection 1
L5-07
oL4
Overtorque Detection 2
L5-07
Fault
Name
Parameters to Disable
Auto Restart
ov
Overvoltage
L5-08
PF
Input Phase Loss
-
rH
Braking Resistor Overheat
-
rr
Dynamic Braking Transistor
Fault
-
STPo
Motor Step-Out Detected
-
Uv1
DC Bus Undervoltage
L5-08
*1
Uv1
is the target for the auto restart process when
L2-01 = 1, 2, 3, or 4 [Power Loss Ride Through Select = Enabled for L2-02 Time,
Enabled while CPU Power Active, Kinetic Energy Backup: L2-02, or Kinetic Energy Backup: CPU Power]
.
■
L5-01: Number of Auto-Restart Attempts
No.
(Hex.)
Name
Description
Default
(Range)
L5-01
(049E)
Number of Auto-Restart
Attempts
Sets the number of times that the drive will try to restart.
0
(0 - 10 times)
The drive resets the number of Auto Restart attempts to 0 in these conditions:
•
The drive operates correctly for 10 minutes after a fault restart.
•
When you manually clear a fault after the drive triggers protective functions.
•
When you re-energize the drive.
■
L5-02: Fault Contact at Restart Select
No.
(Hex.)
Name
Description
Default
(Range)
L5-02
(049F)
Fault Contact at Restart
Select
Sets the function that sends signals to the MFDO terminal set for
Fault [H2-xx = E]
while the drive
is automatically restarting.
0
(0, 1)
0 : Active Only when Not Restarting
1 : Always Active
■
L5-03: Continuous Method Max Restart T
No.
(Hex.)
Name
Description
Default
(Range)
L5-03
(04A0)
Continuous Method Max
Restart T
Sets the time for which the drive will try to restart. If the drive cannot restart inthe time set in
L5-03
,
the drive detects a fault. This is available when
L5-05 = 0 [Auto-Restart Method = Continuous/
Immediate Attempts]
.
10.0 s
(0.5 - 180.0 s)
■
L5-04: Interval Method Restart Time
No.
(Hex.)
Name
Description
Default
(Range)
L5-04
(046C)
Interval Method Restart
Time
Sets the time interval between each Auto Restart attempt. This function is enabled when
L5-05 = 1
[Auto Restart Operation Selection = Use L5-04 Time]
.
10.0 s
(0.5 - 600.0 s)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...