788
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
■
F1-52: Serial Encoder Comm Speed
No.
(Hex.)
Name
Description
Default
(Range)
F1-52
(03D4)
Serial Encoder Comm Speed
Sets the communication speed between the PG-F3 option and the serial encoder.
0
(0 - 2)
Note:
This function is enabled when
F1-50 = 1 or 2 [PG-F3 Option Encoder Type = EnDat Serial Only or HIPERFACE]
.
0 : 1M/9600bps
1 : 500k/19200bps
2 : 1M/38400bps
◆
F2: Analog Input Option
F2 parameters
set the operation of the drive when you use analog input option card AI-A3. The AI-A3 card has 3
input terminals that accept voltages of -10 V to +10 V (20 kΩ) or currents of 4 mA to 20 mA (250 Ω). Install the AI-
A3 card to enable setting very accurate analog references with high resolution.
Refer to the AI-A3 option manual for more information about how to install, wire, and set the AI-A3 card.
WARNING!
Sudden Movement Hazard. Do test runs and examine the drive to make sure that the command references are correct.
If you set the command reference incorrectly, it can cause damage to the drive or serious injury or death.
■
F2-01: Analog Input Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
F2-01
(038F)
Analog Input Function
Selection
Sets the input method for the analog reference used with AI-A3.
0
(0, 1)
Note:
When the AI-A3 card is not mounted in the drive, analog input terminals A1 to A3 on the drive are always enabled. The setting of this
parameter does not have an effect.
0 : 3 Independent Channels
Set
F2-01 = 0
to increase the precision of A/D conversion when you use the functions for terminals A1 to A3 on the
drive as they are. You can input the MFAI signal from terminals V1 through V3 for AI-A3. The functions for
terminals A1, A2, and A3 on the drive are sent to terminals V1, V2, and V3 for AI-A3. Use gain and bias adjustment
when you input current to set signals to have negative numbers.
Note:
•
Set
b1-01 = 1 [Frequency Reference Selection 1 = Analog Input]
to set inputs individually.
•
If
F2-01 = 0
and
b1-01 = 3 [Option PCB]
, the drive will detect
oPE05 [Run Cmd/Freq Ref Source Sel Err]
.
shows the individual input of analog inputs.
H3-xx parameters
set the function to input the analog
reference received from the AI-A3 card and to adjust the gain and bias of these signals.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...