YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
751
■
d4-09: Up/Down 2 Bias Lower Limit
No.
(Hex.)
Name
Description
Default
(Range)
d4-09
(02B0)
RUN
Up/Down 2 Bias Lower
Limit
Sets the lower limit of the Up/Down 2 bias as a percentage of the Maximum Output Frequency.
0.0%
(-99.9 - 0.0%)
The drive saves the set bias lower limit in
d4-06 [Frequency Ref Bias (Up/Down 2)]
. Set
d4-09
to an applicable value
before you use the Up/Down 2 function.
Note:
When
d4-01 = 1 [Freq Reference Hold Selection = Enabled]
and
b1-01 = 0 [Frequency Reference Selection 1 = Keypad]
, the drive will add
the bias value to the frequency reference when it does not receive an Up/Down 2 command for 5 s. Then the drive will reset the value to 0.
If you increase the bias with the Up 2 command and
d4-09 = 0
, you cannot use a Down 2 command to decrease the frequency reference. To
decrease speed in this condition, set a negative lower limit in
d4-09
.
■
d4-10: Up/Down Freq Lower Limit Select
No.
(Hex.)
Name
Description
Default
(Range)
d4-10
(02B6)
Up/Down Freq Lower Limit
Select
Sets the lower frequency limit for the Up/Down function.
0
(0, 1)
0 : Greater of d2-02 or Analog
The higher value between
d2-02 [Frequency Reference Lower Limit]
and an analog input programmed for
Frequency
Reference [H3-02, H3-06, H3-10 = 0]
sets the lower frequency reference limit.
Note:
When you use
External Reference 1/2 Selection [H1-xx = 2]
to switch between the Up/Down function and an analog input as the reference
source, the analog value becomes the lower reference limit when the Up/Down command is active. Set
d4-10 = 1
to isolate the Up/Down
function and the analog input value.
1 : d2-02
You can only use
d2-02
to set the lower limit of the frequency reference.
◆
d5: Torque Control
d5 parameters
set the Torque Control function.
The Torque Control function controls the output torque of the motor. You can use Torque Control for roller drives,
winders, unwinders, conveyors and other machines that use tension control and push/pull applications. When there is
no more material and the machine suddenly has no load, the drive uses Torque Control and the speed limit function to
keep the rotation speed of the motor from increasing.
Set
A1-02 [Control Method Selection]
to one of these values to use Torque Control:
•
3 [Closed Loop Vector]
•
4 [Advanced Open Loop Vector]
•
6 [PM Advanced Open Loop Vector]
•
7 [PM Closed Loop Vector]
Note:
When you use Torque Control and
A1-02 = 4
, use a motor designed for winding applications.
Use one of these methods to enable Torque Control:
•
Set
d5-01 = 1 [Torque Control Selection = Torque Control]
.
•
Set
H1-xx = 71 [Torque Control]
ON.
■
Torque Control Operation
shows the operation principle of Torque Control.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...