886
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
■
H4-03: Terminal FM Analog Output Bias
No.
(Hex.)
Name
Description
Default
(Range)
H4-03
(041F)
RUN
Terminal FM Analog Output
Bias
Sets the bias of the monitor signal that is sent from MFAO terminal FM.
0.0%
(-999.9 - +999.9%)
The analog signal output from the FM terminal is a maximum of ±10 V (or 20 mA). Select the signal level with
H4-
07 [Terminal FM Signal Level Select]
.
■
H4-04: Terminal AM Analog Output Select
No.
(Hex.)
Name
Description
Default
(Range)
H4-04
(0420)
Terminal AM Analog Output
Select
Sets the monitoring number to be output from the MFAO terminal AM.
103
(000 - 999)
Set the
x-xx
part of the
Ux-xx [Monitor]
. For example, set
H4-04 = 103
to monitor
U1-03 [Output Current]
.
Note:
•
You cannot use all of the monitors in all of the control methods.
•
When you use the terminal in through mode, set this parameter to
000
or
031.
You can set the terminal AM output level from the PLC
through MEMOBUS/Modbus communications or the communication option.
■
H4-05: Terminal AM Analog Output Gain
No.
(Hex.)
Name
Description
Default
(Range)
H4-05
(0421)
RUN
Terminal AM Analog Output
Gain
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
50.0%
(-999.9 - +999.9%)
The analog signal output from the AM terminal is a maximum of ±10 V (or 20 mA). Select the signal level with
H4-
08 [Terminal AM Signal Level Select]
.
Examples of possible settings:
When the output current of a monitoring item is 100% (drive rated current) in these examples, the voltage of AM
terminal outputs at 5 V (50% of 10 V). Subsequently, the output current at the time the AM terminal outputs a
maximum voltage of 10 V will be 200% of the drive rated current.
•
H4-04 = 103 [Terminal AM Analog Output Select = Output Current]
•
H4-05 = 50.0%
•
H4-06 = 0.0% [Terminal AM Analog Output Bias = 0.0%]
•
H4-08 = 0 [0 to 10 V]
■
H4-06: Terminal AM Analog Output Bias
No.
(Hex.)
Name
Description
Default
(Range)
H4-06
(0422)
RUN
Terminal AM Analog Output
Bias
Sets the bias of the monitor signal that is sent from MFAO terminal AM.
0.0%
(-999.9 - +999.9%)
The analog signal output from the AM terminal is a maximum of ±10 V (or 20 mA). Select the signal level with
H4-
08 [Terminal AM Signal Level Select]
.
■
H4-07: Terminal FM Signal Level Select
No.
(Hex.)
Name
Description
Default
(Range)
H4-07
(0423)
Terminal FM Signal Level
Select
Sets the MFAO terminal FM output signal level.
0
(0 - 2)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...