12.2 A: Initialization Parameters
654
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Figure 12.6 Dwell Function at Start
Note:
•
If the mechanical operation of the holding brake is slow, use the Dwell Function at Start to prevent brake grinding (friction). Accelerate
after the brake is fully open.
•
When you use V/f Control and Open Loop Vector Control modes, set
b6-01 [Dwell Reference at Start]
>
Frequency Detection 2 (brake
open frequency)
.
•
If the motor torque is not sufficient during start up, use the DC Inject Braking function to secure the motor current (torque) before you start
the motor.
–
b2-02 [DC Injection Braking Current]
recommended setting: 50% to 80% (V/f Control or Open Loop Vector Control)
–
b2-03 [DC Inject Braking Time at Start]
recommended setting: 0.2 s to 0.5 s
DC Injection Braking at Stop, Zero Speed Control Function
Note:
If you disconnect a drive when it is controlling the motor or during DC Injection Braking (Zero speed level), a voltage surge can trigger a
fault. When you use an electromagnetic contactor between the drive and motor, set
L8-07 = 1 or 2 [Output Phase Loss Protection Sel =
Fault when one phase is lost, Fault when two phases are lost]
. If it necessary to disconnect the motor and drive when you stop the elevator,
fully close the holding brake and disconnect the drive during baseblock (that is, while the baseblock signal is ON). This does not apply for
emergency conditions.
Adjustment Parameter
Name
b2-01
DC Injection/Zero SpeedThreshold
b2-02
DC Injection Braking Current
b2-04
DC Inject Braking Time at Stop
H2-xx = 5
Frequency Detection 2
Figure 12.7 DC Injection Braking at Stop, Zero Speed Control Function
Note:
•
If the mechanical operation of the holding brake is slow, use DC Injection Braking (zero speed control when set to closed loop vector) until
the brake is fully closed to prevent rollback.
•
If you cannot hold the load with DC Injection Braking when it is stopped in V/f Control and Open Loop Vector Control modes, use Dwell
Function at Stop.
–
b6-03 [Dwell Reference at Stop]
: Minimum output frequency to 3.0 Hz
When Frequency Detection 2 is OFF, it is less than
L4-01 [Speed Agree Detection Level]
-
L4-02 [Speed Agree Detection Width]
.
–
b6-04 [Dwell Time at Stop]
recommended setting: 0.3 s to 0.5 s
–
b2-04 [DC Inject Braking Time at Stop]
recommended setting: 0.0 s
Torque Compensation (Torque Bias)
This function enters the torque compensation (torque bias) signal that matches a set load from the MFAI terminal in
Closed Loop Vector Control to decrease the overshoot when you open and close the brake. You must detect the load
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...