YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
241
Model
Terminals
Recommended
Gauge
AWG, kcmil
Applicable Gauge
(IP20 Applicable
)
AWG, kcmil
Wire Stripping
mm
Terminal Screw
Tightening Torque
N
∙
m (in
∙
lb)
Size
Shape
2211
R/L1, S/L2, T/L3
250
2 - 250
(2/0 - 250)
37
M10
Hex socket cap
(WAF: 8 mm)
12 - 14
(107 - 124)
U/T1, V/T2, W/T3
300
2 - 300
(3/0 - 300)
37
M10
Hex socket cap
(WAF: 8 mm)
12 - 14
(107 - 124)
-, -, +1, +1
2/0
6 - 2/0
(1/0 - 2/0)
28
M6
Hex socket cap
(WAF: 5 mm)
8 - 9
(71 - 80)
2/0
4 - 2/0
(1 - 2/0)
28
M8
Hex socket cap
(WAF: 6 mm)
8 - 9
(71 - 80)
4
4 - 1/0
(-)
-
M8
Hex bolt (slotted)
9.0 - 11
(79.7 - 97.4)
2257
R/L1, S/L2, T/L3
2/0 × 2P
3 - 4/0 × 2P
(2/0 - 4/0 × 2P)
-
M10
Hex self-locking nut
20
(177)
U/T1, V/T2, W/T3
2/0 × 2P
3 - 4/0 × 2P
(2/0 - 4/0 × 2P)
-
M10
Hex self-locking nut
20
(177)
-, +1
4/0 × 2P
2 - 250 × 2P
(4/0 - 250 × 2P)
-
M10
Hex self-locking nut
20
(177)
+3
1/0 × 2P
4 - 1/0 × 2P
(1/0 × 2P)
-
M10
Hex self-locking nut
20
(177)
3
3 - 350
(-)
-
M10
Hex bolt (slotted)
18 - 23
(159 - 204)
2313
R/L1, S/L2, T/L3
4/0 × 2P
3 - 4/0 × 2P
(2/0 - 4/0 × 2P)
-
M10
Hex self-locking nut
20
(177)
U/T1, V/T2, W/T3
3/0 × 2P
3 - 4/0 × 2P
(2/0 - 4/0 × 2P)
-
M10
Hex self-locking nut
20
(177)
-, +1
250 × 2P
2 - 250 × 2P
(4/0 - 250 × 2P)
-
M10
Hex self-locking nut
20
(177)
+3
1/0 × 2P
4 - 1/0 × 2P
(1/0 × 2P)
-
M10
Hex self-locking nut
20
(177)
2
2 - 350
(-)
-
M10
Hex bolt (slotted)
18 - 23
(159 - 204)
2360
R/L1, S/L2, T/L3
250 × 2P
2/0 - 300 × 2P
(250 - 300 × 2P)
-
M12
Hex self-locking nut
35
(310)
U/T1, V/T2, W/T3
250 × 2P
2/0 - 300 × 2P
(250 - 300 × 2P)
-
M12
Hex self-locking nut
35
(310)
-, +1
350 × 2P
4/0 - 400 × 2P
(300 - 400 × 2P)
-
M12
Hex self-locking nut
35
(310)
+3
3/0 × 2P
1/0 - 4/0 × 2P
(-)
-
M12
Hex self-locking nut
35
(310)
1
1 - 350
(-)
-
M12
Hex bolt (slotted)
32 - 40
(283 - 354)
2415
R/L1, S/L2, T/L3
250 × 2P
2/0 - 300 × 2P
(250 - 300 × 2P)
-
M12
Hex self-locking nut
35
(310)
U/T1, V/T2, W/T3
300 × 2P
2/0 - 300 × 2P
(250 - 300 × 2P)
-
M12
Hex self-locking nut
35
(310)
-, +1
350 × 2P
4/0 - 400 × 2P
(300 - 400 × 2P)
-
M12
Hex self-locking nut
35
(310)
+3
3/0 × 2P
1/0 - 4/0 × 2P
(-)
-
M12
Hex self-locking nut
35
(310)
1
1 - 350
(-)
-
M12
Hex bolt (slotted)
32 - 40
(283 - 354)
*1
For IP20 protection, use wires that are in the range of applicable gauges.
*2
Remove insulation from the ends of wires to expose the length of wire shown.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...