Note:
Refer to
“
d4-01 [Freq Reference Hold Selection]
”
for more information.
Combine Upper/Lower Limits of the Frequency Reference and the Up/Down Commands
Set the upper limit value of the frequency reference to
d2-01 [Frequency Reference Upper Limit]
.
Use an analog input or
d2-02 [Frequency Reference Lower Limit]
to set the lower limit value of the frequency
reference. The configurable values change when the setting for
d4-10 [Up/Down Freq Lower Limit Select]
changes.
When you input a Run command, these are the lower limits of the frequency reference:
•
When the lower limit of the frequency reference is set only for
d2-02
, the drive accelerates the motor to the lower
limit value of the frequency reference when you input the Run command.
•
When the lower limit of the frequency reference is set only for analog input, the drive accelerates the motor to the
lower limit value of the frequency reference when the Run command, and Up command or Down command for the
drive is enabled. When only the Run command is enabled, the motor does not start.
•
When these conditions occur, the drive accelerates the motor to the
d2-02
setting value when the Run command is
input. When the motor accelerates to the setting value of
d2-02
, the motor accelerates to the lower limit value of the
analog input when you enable the Up/Down command.
–
The lower limit value of the frequency reference is set for the analog input and
d2-02
–
The lower limit value of the analog input is higher than the setting value of
d2-02
Note:
Refer to
“
d4-10: Up/Down Freq Lower Limit Select
”
for details.
shows an example of how Up/Down command operates. In this example, the lower limit value of the
frequency reference is set in
d2-02
.
shows the time chart when Freq Reference
Retention Select [d4-01]
is enabled and disabled.
Figure 12.80 Up/Down Command Time Chart
■
11: Down Command
Setting Value
Function
Description
11
Down Command
Sets the command to use a push button switch to decrease the drive frequency reference. You must also set
Setting 10 [Up
Command]
.
ON : Decreases the frequency reference.
OFF : Holds the current frequency reference.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...