This section gives information about message timing.
■
Command Message from Master to Slave
To prevent data loss and overrun, after the master receives a message from the slave, the master cannot send the same
type of command message to the same slave for a selected length of time. The minimum wait time is different for
each type of message. Refer to
to find the minimum wait times.
Table 6.4 Minimum Wait Time to Send a Message
Command Type
Example
Minimum Wait Time
1
•
Operation commands (Run command, stop command)
•
I/O settings
•
Reading the motor and parameter setting values
5 ms
2
Writing a parameter
50 ms
3
Writing of modified data with the Enter command
3 to 5 s
*1
When the drive receives a message in the minimum wait time, it does command type 1 and sends a response message. If the drive
receives command type 2 or command type 3 messages in the minimum wait time, it will trigger a communications error or the drive will
ignore the command.
Figure 6.5 Minimum Wait Time to Send a Message
You must set the timer in the master to measure the length of time for the slave to respond to the master. If you set the
timer, but the slave does not send a response message in a specified length of time, the master will send the message
again.
■
Response Message from Slave
The slave receives the command message from the master then processes the data it received. The slave then waits for
the time set in
H5-06 [Drive Transmit Wait Time]
then sends a response message to the master. If overrun occurs on
the master, increase the wait time set in
H5-06
.
Figure 6.6 Response Wait Time
◆
Message Format
■
Communication Message Description
In MEMOBUS/Modbus communications, the master sends commands to the slave, then the slave responds. The
master and slave send their messages in the configuration in
. The length of the data changes when the
description of the command (function) changes.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...