12.11 o: Keypad-Related Settings
976
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Trend Plot Display
A - Select
Ux-xx [Monitors]
(Monitor 1)
with
o1-24
.
B - Select
Ux-xx [Monitors]
(Monitor 2)
with
o1-25
.
C - Set the maximum value of Monitor 2
with
o1-50
D - Set the minimum value of Monitor 2
with
o1-49
E - Set the time scale with
o1-51
F - Set the minimum value of Monitor 1
with
o1-47
G - Set the maximum value of Monitor 1
with
o1-48
■
o1-01: User Monitor Selection
No.
(Hex.)
Name
Description
Default
(Range)
o1-01
(0500)
RUN
User Monitor Selection
Sets the
U monitor
for the Drive Mode. This parameter is only available when you use an LED
keypad.
106
(104 - 855)
When the drive is in Drive Mode, push
on the keypad to cycle through this data: frequency reference →
rotational direction → output frequency → output current →
o1-01
selection.
Set the
x-xx
part of
Ux-xx
that is shown in the fifth position in Drive Mode. For example, to show
U1-05 [Motor
Speed]
, set
o1-01 = 105
.
Note:
The monitors that you can select are different for different control methods.
■
o1-02: Monitor Selection at Power-up
No.
(Hex.)
Name
Description
Default
(Range)
o1-02
(0501)
RUN
Monitor Selection at Power-
up
Sets the monitor item that the keypad screen shows after energizing the drive. Refer to
“
U: Monitors
”
for information about the monitor items that the keypad screen can show. This parameter is only
available when you use an LED keypad.
1
(1 - 5)
1 : Frequency Reference (U1-01)
2 : Direction
3 : Output Frequency (U1-02)
4 : Output Current (U1-03)
5 : User Monitor (o1-01)
Shows the monitor item selected in
o1-01 [User Monitor Selection]
.
■
o1-03: Frequency Display Unit Selection
No.
(Hex.)
Name
Description
Default
(Range)
o1-03
(0502)
Frequency Display Unit
Selection
Sets the display units for the frequency reference and output frequency.
Determined by A1-02
(0 - 3)
G
F
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...