YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
321
Code
Name
Causes
Possible Solutions
The setting of
n8-84 [Polarity Detection Current]
is
too low.
Increase the
n8-84
setting from the default. Consult the motor
manufacturer for information about maximum setting values.
Pole Position Detection failed.
If you are using an IPM motor, do High Frequency Injection Auto-
Tuning.
The PG option card or the encoder on the motor side
is damaged.
Repair the wiring and re-energize the drive, then replace the PG
option card or the PG if the problem continues.
Note:
•
The drive detects this error if the pulses in the opposite direction of the speed reference are more than the value set in
F1-19
.
•
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
dv7
Polarity Judge Timeout
There is a disconnection in the motor coil winding.
Measure the motor line-to-line resistance and replace the motor if a
coil is disconnected.
The screws on the drive output terminals are loose.
Tighten the terminal screws to the correct tightening torque.
Note:
•
The drive detects this error if it cannot detect polarity in a pre-set length of time.
•
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
dWF1
EEPROM Memory DWEZ Data
Error
There is an error in the EEPROM peripheral circuit.
•
Re-energize the drive.
•
If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
There is a problem with the EEPROM data.
Set
A1-03 = 2220, 3330 [Initialize Parameters = 2-Wire
Initialization, 3-Wire Initialization]
to initialize the drive, then
upload the DriveWorksEZ project to the drive again.
Note:
•
The drive detects this error if there is an error in the DriveWorksEZ program that was saved to EEPROM.
•
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
dWF2
DriveWorksEZ Fault 2
There was a fault in the DriveWorksEZ program.
Examine the DriveWorksEZ program and remove the cause of the
fault. This is not a drive fault.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
dWF3
DriveWorksEZ Fault 3
There was a fault in the DriveWorksEZ program.
Examine the DriveWorksEZ program and remove the cause of the
fault. This is not a drive fault.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
dWFL
DriveWorksEZ Fault
There was a fault in the DriveWorksEZ program.
Examine the DriveWorksEZ program and remove the cause of the
fault. This is not a drive fault.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
E5
MECHATROLINK Watchdog Timer
Err
The drive detected a watchdog circuit exception while
it received data from the controller.
Examine the MECHATROLINK cable connection. If this error
occurs frequently, examine the wiring and decrease the effects of
electrical interference as specified by these manuals:
•
MECHATROLINK-II Installation Guide (MECHATROLINK
Members Association, manual number MMATDEP011)
•
MECHATROLINK-III Installation Manual (MECHATROLINK
Members Association, publication number MMATDEP018)
Note:
•
Do a Fault Reset to clear the fault.
•
If the drive detects this fault, it will operate the motor as specified by the stop method set in
F6-25 [MECHATROLINK Watchdog Error Sel]
.
Code
Name
Causes
Possible Solutions
EF0
Option Card External Fault
The communication option received an external fault
from the controller.
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input from the controller.
A programming error occurred on the controller side.
Examine the operation of the controller program.
Note:
•
The drive detects this fault if the alarm function on the external device side is operating.
•
Do a Fault Reset to clear the fault.
•
If the drive detects this fault, it will operate the motor as specified by the stop method set in
F6-03 [Comm External Fault (EF0) Select]
.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...