KEB Ride-Thru End Detection
Parameter
L2-01 [Power Loss Ride Through Select]
and a digital input programmed for KEB set the KEB function
end detection.
Use the Momentary Power Loss Ride-Thru Time to Cancel KEB Operation
shows an example with this configuration:
•
L2-01 = 3 [Kinetic Energy Backup: L2-02]
is set.
•
KEB Ride-Thru is not used.
The drive starts deceleration through KEB operation. When the time set in
L2-10 [Minimum KEB Time]
expires, the
drive stops the KEB operation and then it accelerates the motor again until it is at the frequency reference value used
before the power loss.
If you do not return the DC bus voltage in the time set in
L2-02 [Power Loss Ride Through Time]
, the drive detects
Uv1 [DC Bus Undervoltage]
and the drive turns off its output.
Figure 12.124 Cancel the KEB Operation after the Momentary Power Loss Ride-Thru Time Is Expired without KEB Ride-
Thru
*1
When
L2-07 = 0.00 [Kinetic Energy Backup Accel Time = 0.00 s]
, the drive accelerates again as specified by the
applicable
Acceleration Time [C1-01, C1-03, C1-05, C1-07]
, and usual operation continues.
Use the Momentary Power Loss Ride-Thru Time and KEB Ride-Thru to Cancel KEB Operation
shows an example with this configuration:
•
L2-01 = 3
.
•
Use
KEB Ride-Thru 1 [H1-xx = 65, 66]
or
KEB Ride-Thru 2 [H1-xx = 7A, 7B]
.
The drive starts deceleration through KEB operation. The drive decelerates for the time set in parameter
L2-10
, then it
measures the DC bus voltage and the status of the digital input terminal set for KEB Ride-Thru. When the DC bus
voltage is less than the level set in
L2-11 [KEB DC Bus Voltage Setpoint]
, or if the KEB digital input is active, KEB
deceleration continues. When the DC bus voltage is more than the level set in
L2-11
, the drive ends KEB operation.
The drive accelerates the motor to the frequency reference value before the power loss, and usual operation continues.
If the time set in
L2-02
is expired, the drive detects
Uv1
. When you cancel the KEB Ride-Thru, the motor accelerates
again, and usual operation continues.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...