Note:
•
Use UL-Listed, vinyl-coated insulated copper wires for operation with a continuous maximum permitted temperature of 75 °C at 600 V.
•
Remove all unwanted objects that are near the terminal block connections.
•
Remove the insulation from the connection wires to the wire stripping lengths shown in the manual.
•
Do not use bent or crushed wires. Remove the damaged end of the wire before you use it. Incorrect connections can cause death or serious
injury from fire.
•
Do not solder stranded wire. Soldered wire connections can become loose over time and cause unsatisfactory drive performance.
•
If you use stranded wire, make sure that all of the wire strands are in the connection. Also, do not twist the stranded wire too much.
Incorrect connections can cause death or serious injury from fire.
•
Put the wire all the way into the terminal block. Remove the insulation from the wire to the recommended wire stripping length to fit the
wire with insulation in the plastic housing.
•
Use a torque driver, torque ratchet, or torque wrench for the screws. A slotted driver or a hex tool will be necessary to wire the screw clamp
terminal. Use applicable tools as specified by the recommended conditions in the product manual.
•
If you use power tools to tighten the terminal screws, use a low speed setting (300 to 400 r/min). Failure to obey can cause damage to the
terminal screws.
•
Users can purchase wiring tools from Yaskawa. Contact Yaskawa or your nearest sales representative for more information.
•
Wire gauges on existing drive models to be replaced may not match wire gauge ranges on new drives. Contact Yaskawa or your nearest
sales representative for more information about the connection procedures.
•
Do not tighten the terminal screws at an angle of 5 degrees or more. Failure to obey can cause damage to the terminal screws.
Figure 5.8 Permitted Angle
•
Put the bit all the way into the hex socket to tighten the hex socket cap screw.
•
When you tighten slotted screws, hold the straight-edge screwdriver perpendicularly to the screw. Make sure that you align the end of the
straight-edge screwdriver with the screw groove.
Figure 5.9 Tightening Slotted Screws
•
After connecting the wires to the terminal block, lightly pull on the wires to make sure that they do not come out of the terminals.
•
Remove the correct section of the wiring cover to make wiring easier.
•
Do not let strain on the wiring cause damage. Use a strain relief near the wiring to release the tension. Refer to
for an example.
A - Cable clamp
Figure 5.10 Strain Relief Example
5°
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...